Short answer

The circuit breaker working principle in brief: a circuit breaker is a switch that can carry normal current and automatically interrupt fault current. When it trips, its contacts separate and an arc forms between them. The breaker cools and stretches the arc in a quenching medium such as air, vacuum or SF6 gas, so that the arc goes out at a current zero and does not restrike.

What a circuit breaker does

A circuit breaker has four duties:

  • Carry its rated current continuously without overheating.
  • Make (close onto) a circuit, including one that already has a fault on it.
  • Break normal load current when switched off.
  • Interrupt short-circuit current quickly enough to limit damage, when commanded by its own trip unit or by an external protection relay.

Circuit breaker working principle: how it interrupts current

1. Detection and tripping

Low voltage breakers usually have a built-in trip unit. A thermal element (a bimetal strip) bends with sustained overload current and releases the latch after a delay. A magnetic element (a coil) responds almost instantly to high short-circuit currents. Electronic trip units do the same job using current sensors and a microprocessor.

Medium and high voltage breakers are tripped by external protection relays, which measure current and voltage through instrument transformers and energise the breaker trip coil.

2. Contact separation and the arc

The trip mechanism releases stored energy, usually in springs, to drive the contacts apart. Current does not stop when the contacts part. The voltage across the small gap ionises the medium, and current continues to flow as an arc, a column of very hot conducting plasma.

3. Arc extinction

In an AC circuit the current passes through zero twice in each cycle. At a current zero the arc briefly loses its energy supply. Interruption succeeds if the gap regains its insulating strength faster than the transient recovery voltage (TRV) rises across it. If it does not, the arc restrikes and the breaker tries again at the next current zero.

Breakers help the gap recover by:

  • Lengthening the arc, for example by driving it into arc chutes with splitter plates.
  • Cooling it with gas flow or by contact with cold surfaces.
  • Removing the ionised particles, which happens very quickly in a vacuum.

Types of circuit breaker

By voltage and construction

TypeTypical voltage rangeArc quenchingTypical use
MCB (miniature circuit breaker)Low voltage, small currentsArc chute in airFinal circuits in buildings
MCCB (moulded case circuit breaker)Low voltage, up to a few thousand amperesArc chute in airFeeders, motor and panel protection
ACB (air circuit breaker)Low voltage main incomersArc chutes in open airMain switchboards
VCB (vacuum circuit breaker)Medium voltage, commonly up to about 36 kVVacuum interrupterMV switchgear and motor feeders
SF6 circuit breakerMedium and high voltage, up to the highest transmission levelsSulphur hexafluoride gasHV substations, gas insulated switchgear
Oil circuit breakerMedium and high voltageMineral oilOlder installations, largely replaced

SF6 is an excellent insulating and arc quenching gas, but it is a very strong greenhouse gas. Manufacturers are therefore developing vacuum and alternative gas designs for higher voltages.

MCB trip curves

IEC 60898-1 defines the instantaneous (magnetic) trip range of MCBs as a multiple of rated current In:

CurveInstantaneous trip rangeTypical loads
B3 to 5 × InResistive loads, lighting, long cables
C5 to 10 × InGeneral commercial and small motor loads
D10 to 20 × InHigh inrush loads such as transformers and large motors

Key ratings

  • Rated voltage and current: the system voltage and continuous current the breaker is designed for.
  • Breaking capacity: the highest fault current it can safely interrupt. For LV breakers IEC 60947-2 defines the ultimate breaking capacity Icu and the service breaking capacity Ics.
  • Making capacity: the peak current it can close onto without damage.
  • Short-time withstand current Icw: the current it can carry for a stated time, which allows selective (time-graded) tripping.

Selecting breaking capacity

The breaking capacity must be at least the prospective short-circuit current at the point of installation. Close to a distribution transformer, a simple estimate assumes an infinite source behind the transformer:

IFL=S3 V,Isc≈IFLZpuI_{FL} = \frac{S}{\sqrt{3}\,V}, \qquad I_{sc} \approx \frac{I_{FL}}{Z_{pu}}
Worked example
Given
1000 kVA transformer, 415 V secondary, impedance 5 percent.
Find
Approximate fault current at the transformer LV terminals.
Assumptions
Infinite upstream source (no source impedance); bolted three-phase fault; cable impedance ignored.
Solution
IFL = 1,000,000 / (1.732 × 415) = 1391 A
Isc ≈ 1391 / 0.05 = 27,820 A
Answer
About 27.8 kA, so the main incomer needs a breaking capacity above this, for example a standard 36 kA or higher rating
Limitations
This estimate is on the safe side because it ignores source impedance. A full calculation to IEC 60909 includes the network, cables and motor contributions.

Selectivity between breakers

In a radial low voltage system, breakers are installed in series: a main incomer, feeder breakers and final circuit breakers. For a fault on a final circuit, only the breaker closest to the fault should trip, so that the rest of the installation stays in service. This is called selectivity or discrimination.

  • Current selectivity relies on the downstream breaker tripping at a lower current than the upstream one. It is often only partial, because large fault currents can exceed both instantaneous settings.
  • Time selectivity delays the upstream breaker’s short-circuit trip, which requires it to withstand the fault current for that time (its Icw rating).
  • Energy selectivity uses current-limiting downstream breakers that clear the fault so fast that the upstream breaker does not see enough energy to trip.

Manufacturers publish selectivity tables that show which combinations of their breakers are selective, and up to which fault current.

Circuit breaker or fuse?

FeatureCircuit breakerFuse
After operationReset or recloseReplace the fuse link
Remote operation and relay trippingYesNo
Adjustable settingsYes, on many MCCBs and ACBsNo
Current limitingSome designsExcellent, very fast for high faults
Cost for high breaking capacityHigherLower

Maintenance and testing

Breakers are inspected and tested at intervals set by the manufacturer. Typical checks include contact resistance measurement, operating time tests, insulation resistance tests, trip unit testing by secondary or primary injection, and inspection of the operating mechanism and arc chutes. For vacuum interrupters, vacuum integrity is checked with a high voltage test.

Frequently asked questions

What is the difference between a circuit breaker and a fuse?

Both interrupt fault current. A fuse melts and must be replaced after it operates, while a circuit breaker opens mechanically and can be reset or reclosed. Breakers can also be operated by protection relays and used as switches.

What is the difference between an isolator and a circuit breaker?

An isolator is an off-load device that provides a visible break for safe maintenance. A circuit breaker can make and break load and fault currents. Isolators must only be operated after the breaker has opened the circuit.

Why is it harder to interrupt DC than AC?

AC current passes through zero twice every cycle, which gives the arc a natural point to go out. DC current has no zero, so the breaker must force the current down by building up a high arc voltage, which needs special designs and ratings.

References

  1. IEC 60947-2, Low-voltage switchgear and controlgear, Part 2: Circuit-breakers
  2. IEC 60898-1, Circuit-breakers for overcurrent protection for household and similar installations
  3. IEC 62271-100, High-voltage switchgear and controlgear, Part 100: Alternating-current circuit-breakers
  4. C. H. Flurscheim (ed.), Power Circuit Breaker Theory and Design, IET