Bernoulli Equation in Flow Measurement: Square Root of DP
The Bernoulli equation in flow measurement links the pressure drop across a restriction to the rise in fluid velocity: ΔP = ½ρ(v₂² − v₁²). Combined with continuity, it gives Q = C·E·A₂·√(2ΔP/ρ). Flow therefore follows the square root of differential pressure, which is why orifice, venturi and pitot meters need square root extraction.
Differential pressure (DP) meters are still the most widely installed flowmeters in process plants. An orifice plate, a DP transmitter and two impulse lines are cheap, well understood and backed by a full international standard. All of it rests on one result from fluid mechanics. The general Bernoulli equation covers derivation and assumptions; this article follows it into the instrument loop, from the pipe to the 4 to 20 mA signal.
The Bernoulli equation in flow measurement: deriving the DP flow equation
Take a horizontal pipe of area A₁ with a restriction of area A₂. For steady, incompressible, frictionless flow, Bernoulli between the upstream tapping (1) and the throat (2) gives:
The same volume passes both sections, so continuity says A₁v₁ = A₂v₂. Write the diameter ratio as β = d/D, so v₁ = β²v₂. Substituting:
Multiplying by the throat area gives the ideal volume flow. A real meter loses some energy to friction, and behind an orifice the jet keeps contracting to a vena contracta smaller than the bore. A discharge coefficient C, found by calibration, corrects for both:
E is the velocity of approach factor. For gases, ISO 5167 adds an expansibility factor ε and writes the equation as mass flow:
Everything in front of the square root is fixed by the meter and the fluid. That leaves the part an instrument engineer cares about:
Why flow follows the square root of DP
The kinetic energy term ½ρv² is squared in velocity, so pressure drop grows as the square of flow. Double the flow and the DP rises four times. Halve it and the DP falls to a quarter.
| Flow, % of max | DP, % of span | 4 to 20 mA from a linear DP transmitter |
|---|---|---|
| 100 | 100 | 20.0 mA |
| 70.7 | 50 | 12.0 mA |
| 50 | 25 | 8.0 mA |
| 30 | 9 | 5.44 mA |
| 10 | 1 | 4.16 mA |
This square law is the reason DP meters have limited turndown ratio. At 10% flow the transmitter sees just 1% of its span.
Square root extraction
A DP transmitter measures pressure, but operators and controllers need flow. Somewhere in the loop the signal must be square rooted:
- In the transmitter. Most smart DP transmitters have a square root output mode, so the 4 to 20 mA signal is already linear in flow.
- In the DCS or PLC. The transmitter sends linear DP and the control system applies the square root in its input block.
- In older systems, a separate square root extractor module or a gauge with a square root scale did the job.
Only do it in one place. Applying the square root twice, once in the transmitter and again in the DCS, is a common commissioning mistake that makes the flow reading too high at low flow.
Near zero DP the square root curve is very steep, so a tiny offset or noise produces a large flow reading. A low flow cutoff, typically a few percent of flow, forces the output to zero below that point.
For the plain relation between pipe area, velocity and flow rate, see the flow rate formula on instrumentationblog.in.
The same equation in other DP meters
- Venturi tube. A smooth converging cone, throat and long diverging cone. C is about 0.98 to 0.995 and most of the DP is recovered downstream.
- Flow nozzle. A rounded inlet without the long diffuser. C is high, near 0.99, but recovery is poorer than a venturi.
- Pitot tube and averaging pitot. The impact port brings the flow to rest, so it reads stagnation pressure. The difference from static pressure is ½ρv², giving v = √(2ΔP/ρ) at that point, or across the pipe for an averaging probe.
- Elbow meter. Centrifugal force in a bend makes the outer wall pressure higher than the inner. The DP still follows a square law, though the coefficient usually needs field calibration.
Permanent pressure loss
Not all the DP is lost. Downstream of the restriction the fluid slows and pressure partly recovers. For an orifice plate, ISO 5167-2 gives an approximation for the permanent loss:
At β = 0.6 that is about 62% of the measured DP. A venturi loses typically only 5 to 20%, which matters for pumping cost on large lines.
Worked example: water through an orifice plate
- Given
- Water at 20°C (ρ = 998 kg/m³) flows in a 100 mm bore pipe through a concentric orifice of d = 60 mm. The DP transmitter reads 250 mbar (25,000 Pa). Take C = 0.61.
- Find
- Volume flow, mass flow and approximate permanent pressure loss.
- Assumptions
- Fully developed turbulent flow, incompressible liquid (ε = 1), C constant at this Reynolds number.
- Solution
- β = 60 ÷ 100 = 0.6, β⁴ = 0.1296
E = 1 ÷ √(1 − 0.1296) = 1.0719
A₂ = π/4 × 0.06² = 0.002827 m²
√(2ΔP/ρ) = √(2 × 25,000 ÷ 998) = 7.078 m/s
Q = 0.61 × 1.0719 × 0.002827 × 7.078 = 0.01309 m³/s = 47.1 m³/h
q_m = 0.01309 × 998 = 13.06 kg/s
Permanent loss ≈ (1 − 0.6^1.9) × 25,000 ≈ 15,500 Pa = 155 mbar - Answer
- About 47.1 m³/h (13.1 kg/s) of water, with roughly 155 mbar of the 250 mbar DP lost permanently
- Limitations
- C was assumed. For custody or design work, calculate C from the ISO 5167 Reader-Harris/Gallagher equation and iterate with the Reynolds number; check straight pipe lengths too.
The pipe velocity here is 1.67 m/s, a Reynolds number of about 166,000, comfortably turbulent.
Key formulas for Bernoulli in flow measurement
| Quantity | Formula | Symbols and units |
|---|---|---|
| Bernoulli across a restriction | ΔP = ½ρ(v₂² − v₁²) | ΔP in Pa, ρ in kg/m³, v in m/s |
| Continuity | A₁v₁ = A₂v₂ | A in m² |
| Beta ratio | β = d ÷ D | d = bore, D = pipe internal diameter |
| Velocity of approach factor | E = 1 ÷ √(1 − β⁴) | Dimensionless |
| Volume flow | Q = C·E·A₂·√(2ΔP/ρ) | C = discharge coefficient, Q in m³/s |
| Mass flow (ISO 5167) | q_m = C·E·ε·(π/4)d²·√(2ΔPρ₁) | ε = expansibility factor, q_m in kg/s |
| Square root law | Q = K√ΔP, so Q/Q_max = √(ΔP/ΔP_max) | K = meter constant |
| Pitot tube velocity | v = √(2ΔP/ρ) | ΔP = stagnation minus static pressure |
| Orifice permanent loss | Δϖ ≈ (1 − β^1.9)ΔP | Approximation from ISO 5167-2 |
Bernoulli in flow measurement interview and viva questions
- Derive why flow is proportional to √ΔP. Bernoulli gives ΔP = ½ρ(v₂² − v₁²); continuity relates v₁ to v₂; solving gives v₂ ∝ √ΔP, and Q = A₂v₂.
- What does a 12 mA signal mean on a DP flow loop? If the transmitter output is linear DP, it means 50% DP or 70.7% flow. If square root extraction is on, it means 50% flow.
- Why is the orifice discharge coefficient about 0.6? The jet keeps contracting after the bore to a vena contracta, so the effective flow area is smaller than the bore area, and friction adds a small loss.
- What is the beta ratio and its usual range? The bore diameter divided by pipe diameter. ISO 5167 orifice plates are generally used between about 0.1 and 0.75.
- Why is a low flow cutoff needed? The square root curve is steep near zero, so small DP offsets or noise appear as a large flow; the cutoff forces the reading to zero.
- Why does a venturi have lower permanent pressure loss than an orifice? Its long diverging cone slows the fluid gradually and recovers most of the pressure, while the orifice jet breaks up into eddies that waste energy.
- What happens if square root extraction is applied in both the transmitter and the DCS? The flow reading becomes the fourth root of DP, reading too high at all flows below maximum.
Frequently asked questions
Why is flow proportional to the square root of differential pressure?
Bernoulli's equation says the pressure drop across a restriction equals the gain in kinetic energy per unit volume, which is ½ρv². Velocity, and so volume flow, therefore varies with the square root of the pressure drop. Doubling the flow raises the DP four times.
What is the discharge coefficient of an orifice plate?
It corrects the ideal Bernoulli flow for the vena contracta and friction. For a sharp edged concentric orifice it is usually close to 0.6, while a classical venturi tube is about 0.98 to 0.995. ISO 5167 gives equations for C as a function of beta ratio and Reynolds number.
What is square root extraction in a DP transmitter?
It is a function in the transmitter, control system or a separate module that takes the square root of the DP signal so the output is linear in flow. With it, a 12 mA signal on a 4 to 20 mA loop means 50% flow; without it, 12 mA means 50% DP, which is about 70.7% flow.
Can Bernoulli's equation be used for gas flow measurement?
Yes, with an expansibility factor ε that corrects for the density change of the gas through the restriction. ISO 5167 includes ε in the mass flow equation; it is 1 for liquids and slightly below 1 for gases.
References
- ISO 5167-1:2022 Measurement of fluid flow by means of pressure differential devices inserted in circular cross section conduits running full, Part 1: General principles and requirements
- ISO 5167-2:2022 Part 2: Orifice plates
- R. C. Baker, Flow Measurement Handbook, 2nd ed., Cambridge University Press
- T. R. Kuphaldt, Lessons In Industrial Instrumentation, Flow measurement chapter, control.com textbook (CC BY 4.0)
- B. G. Liptak (ed.), Instrument Engineers' Handbook, Vol. 1: Process Measurement and Analysis, 4th ed., CRC Press