Instrumentation and Control Engineering Fundamentals

Turndown Ratio: Formula, Examples and Typical Values

Turndown Ratio: Formula, Examples and Typical Values: featured diagram
Short answer

Turndown ratio is the maximum value an instrument can measure accurately divided by the minimum value it can measure with the same accuracy: TR = Q_max / Q_min. A flowmeter that reads 100 m³/h down to 10 m³/h within its accuracy limit has a 10:1 turndown. Higher turndown means a wider usable range.

Every instrument has a range where it works well. Push it too low and the signal sinks into noise, friction or offset error. Turndown ratio puts a number on that usable range, and it is one of the first figures an instrument engineer checks on a flowmeter datasheet. A meter with too little turndown will read well at design flow and badly during start-up, night shifts or reduced throughput.

Watch: What is turndown ratio in 18 seconds

Turndown ratio formula

TR=QmaxQminTR = \frac{Q_{max}}{Q_{min}}

where Q_max is the highest flow (or pressure, level, heat output) the device handles within its stated accuracy, and Q_min is the lowest. The result is written as a ratio such as 10:1.

The same idea works in the other direction for an application. If a gas line runs between 100,000 and 1,000,000 m³ per day, the process needs a turndown of 10:1, so the meter must offer at least that. If the chosen meter tops out at 2,000,000 m³ per day, it must reach 100,000 m³ per day accurately, which means 20:1 from that meter.

Turndown is also quoted for things that are not measuring devices. A burner with 4:1 turndown can fire down to a quarter of its maximum heat output and still burn cleanly. A control valve’s rangeability is the ratio of the largest to the smallest flow it can control.

Turndown and rangedown on a transmitter

On a pressure or DP transmitter the word means something slightly different. Here it is the rangedown: the upper range limit (URL) of the sensor divided by the smallest span you are allowed to calibrate it to.

TD=URLminimum spanTD = \frac{URL}{\text{minimum span}}

A DP transmitter with a 2500 mbar URL and a 25 mbar minimum span has a 100:1 turndown. That lets one model cover many duties, which suits spares stock. The catch is accuracy. Datasheets give accuracy as a percentage of calibrated span, often with an extra term that grows once the span drops below a stated fraction of URL. Set the same unit to a span of 25 mbar and its error, as a share of that span, can be several times larger than at full URL. So high transmitter turndown buys flexibility, not free precision.

Why DP flowmeters have low turndown

Orifice plates, venturis, nozzles and pitot tubes all work on the Bernoulli equation, and their differential pressure rises with the square of flow:

ΔP∝Q2⇒Q∝ΔP\Delta P \propto Q^2 \quad\Rightarrow\quad Q \propto \sqrt{\Delta P}

At 50% flow the DP is 25% of full scale. At 10% flow it is only 1%. The transmitter’s error is a fixed slice of its DP span, so at low flow that slice becomes a large share of a tiny signal. Square root extraction halves the relative error when it converts DP to flow, but it cannot rescue a signal that has almost vanished.

50%10%100%025%100%0Flow, % of maximumDP, % of spanErrorswampssignalUsable range, about 4.5:150% flow = 25% DP10% flow= 1% DP
DP rises with the square of flow. Below about 22% flow (red), a 0.1% of span transmitter error exceeds 1% of the flow reading.
Download diagram (WebP)

That is why a single orifice meter is usually good for about 3:1 to 5:1. Plants that need more either fit two DP transmitters with different spans on the same orifice (a “stacked” arrangement that switches between them) or choose a different meter.

Typical turndown ratios

Figures below are typical published values. Makers quote their own, and the ratio always belongs with the accuracy it was stated at.

DeviceTypical turndownWhat limits it
Orifice plate with one DP transmitter3:1 to 5:1Square law, DP falls to a tiny signal
Venturi or flow nozzle4:1 to 10:1Square law, same as orifice
Turbine meter10:1Bearing friction and drag at low flow
Vortex meter10:1 to 20:1Low Reynolds number stops vortex shedding
Rotary positive displacement meter10:1 to 80:1Leakage past rotors at low flow
Multipath ultrasonic meterabout 50:1Timing resolution at low velocity
Magnetic flowmeter30:1 to 100:1 or moreSignal noise at very low velocity
Coriolis mass flowmeter100:1 or moreZero stability
Thermal mass flowmeter100:1 and aboveSensor noise and heat loss effects

For an introduction to how each of these meters works, see the flow measurement section at instrumentationblog.in.

Worked example: how low can an orifice meter read?

Worked example
Given
An orifice meter is calibrated for 0 to 250 mbar DP at maximum flow. The DP transmitter accuracy is ±0.1% of span. The user wants the flow reading to stay within ±1% of reading.
Find
The DP error at 10% flow, and the turndown the meter can deliver.
Assumptions
Only transmitter error is considered; the orifice coefficient is taken as constant. Since Q ∝ √ΔP, the relative flow error is half the relative DP error.
Solution
Transmitter error = 0.001 × 250 = 0.25 mbar
At 10% flow: ΔP = 0.1² × 250 = 2.5 mbar, so DP error = 0.25 ÷ 2.5 = 10% and flow error ≈ 5%
For a 1% flow error the DP error must be 2% or less: ΔP_min = 0.25 ÷ 0.02 = 12.5 mbar
Q_min / Q_max = √(12.5 ÷ 250) = 0.224, so TR = 1 ÷ 0.224 ≈ 4.5
Answer
At 10% flow the reading may be off by about 5%; for ±1% of reading the meter manages only about 4.5:1 turndown
Limitations
The discharge coefficient also drifts at low Reynolds number, and installation effects add error, so real turndown is often a little lower.

Key formulas for turndown ratio

QuantityFormulaSymbols and units
Turndown ratioTR = Q_max ÷ Q_minQ in any consistent flow unit, TR written as TR:1
Transmitter turndown (rangedown)TD = URL ÷ span_minURL and span in the same pressure unit
DP flow relationQ = K √ΔPK = meter constant, ΔP in Pa or mbar
Relative flow error from DP errorδQ/Q ≈ ½ × δΔP/ΔPFractions or percent
Minimum flow for a target errorQ_min/Q_max = √(e_tx ÷ (2 × e_Q))e_tx = transmitter error as a fraction of span, e_Q = allowed flow error as a fraction of reading

How to choose a meter with the right turndown

  1. Find the real minimum and maximum flows, including start-up, turndown operation and future capacity.
  2. Divide them to get the required turndown, then allow some margin.
  3. Compare with the meter’s turndown at the accuracy you need, not its widest headline figure.
  4. Check that the maximum flow sits comfortably inside the meter range and not right at its top, since oversizing a meter eats turndown at the bottom.
  5. For DP meters needing more than about 5:1, consider stacked transmitters or another technology.

A low flow cutoff in the transmitter or control system is usually set near the bottom of the usable range, so the reading drops to zero instead of showing noise when the line is shut.

Turndown ratio interview and viva questions

  1. Define turndown ratio. It is the maximum measurable value divided by the minimum value measured within the stated accuracy, written as a ratio such as 10:1.
  2. Why does an orifice plate have low turndown? DP varies with the square of flow, so at 10% flow the DP is only 1% of span and the transmitter’s fixed error becomes a large share of the signal.
  3. What is the turndown of a DP transmitter? It is the upper range limit divided by the minimum calibratable span, for example 2500 mbar ÷ 25 mbar = 100:1.
  4. Does a 100:1 transmitter turndown give 100:1 flow turndown on an orifice? No. Flow turndown is limited by the square law and by accuracy at low DP, which keeps an orifice meter near 3:1 to 5:1.
  5. How can you extend the range of an orifice meter? Fit two DP transmitters with different spans on the same orifice and switch between them, or use a meter with higher turndown such as a Coriolis or magnetic flowmeter.
  6. What is the turndown required if flow varies from 20 to 160 m³/h? 160 ÷ 20 = 8, so 8:1.

Frequently asked questions

What is a good turndown ratio for a flowmeter?

It depends on how much the process flow varies. A meter only needs a turndown a little above the ratio of the highest to the lowest flow you must measure accurately. Orifice plates give about 3:1 to 5:1, turbine meters about 10:1, multipath ultrasonic meters about 50:1, and Coriolis and magnetic meters often 100:1 or more.

Is turndown ratio the same as rangeability?

In flow measurement the two words are usually used for the same idea: maximum flow divided by the minimum flow measured within the stated accuracy. Some writers keep rangeability for the ratio quoted by the maker and turndown for the ratio an application actually uses, so always check what a datasheet means.

How do you write a turndown ratio?

As a ratio with 1 on the right, for example 10:1, read as ten to one. A device with a maximum of 100 m³/h and a minimum of 10 m³/h has a turndown of 10:1.

Why is a high transmitter turndown not always useful?

Accuracy is usually stated as a percentage of the calibrated span. When a transmitter is ranged down to a small span, the fixed part of its error becomes a larger share of that span, so a 100:1 rangedown can carry several times the error of the same unit set near its upper range limit.

References

  1. T. R. Kuphaldt, Lessons In Industrial Instrumentation, Instrument turndown, control.com textbook (CC BY 4.0)
  2. B. G. Liptak (ed.), Instrument Engineers' Handbook, Vol. 1: Process Measurement and Analysis, 4th ed., CRC Press
  3. R. C. Baker, Flow Measurement Handbook, 2nd ed., Cambridge University Press
  4. ISO 5167-2:2022 Measurement of fluid flow by means of pressure differential devices, Part 2: Orifice plates